Hazard Classification & Its Design Impact

The first step in designing any suppression system is determining the facility hazard classification per NFPA 13, as adopted in the UAE Civil Defence Code:

Light Hazard

Offices, churches, hospitals, hotels, schools — limited combustible content.

  • Design Density: 4.1 L/min/m²
  • Design Area: 139 m²
  • Max area per sprinkler head: 18.6 m²
  • Max distance from wall: 2.3 m

Ordinary Hazard Group 1

Car parks, bakeries, electronics manufacturing, laundry facilities.

  • Design Density: 8.2 L/min/m²
  • Design Area: 139 m²
  • Max area per head: 12.1 m²

Ordinary Hazard Group 2

General merchandise warehouses, metalworking, rubber processing, car showrooms.

  • Design Density: 12.2 L/min/m²
  • Design Area: 139 m²
  • Max area per head: 12.1 m²

Extra Hazard Group 1

Repair workshops, sawmills, die casting, petroleum distillation.

  • Design Density: 16.3 L/min/m²
  • Design Area: 232 m²
  • Max area per head: 9.3 m²

Extra Hazard Group 2

Flammable liquid storage warehouses, furniture manufacturing, dip-coating operations.

  • Design Density: 24.5 L/min/m²
  • Design Area: 232 m²
  • Max area per head: 9.3 m²

Sprinkler Head Types & Classifications

Pendent Sprinkler

Installed with head facing down — most common type. Deflector must be 25–305 mm from ceiling. No obstruction permitted within 460 mm below deflector.

Upright Sprinkler

Installed with head facing up — suited for exposed pipework in warehouses. Deflector 25–100 mm above the centre of the head.

Sidewall Sprinkler

Mounted on walls — suited for narrow corridors and rooms with limited ceiling access. Fan-shaped forward and side discharge pattern.

Concealed Sprinkler

Recessed into ceiling with a fusible cover plate (typically 57°C) — used in hotels and premium offices for aesthetic purposes.

ESFR Sprinkler (Early Suppression Fast Response)

Specifically designed for high-piled storage warehouses (above 3.5 m storage height). Eliminates the need for in-rack sprinklers. Coverage up to 9.3 m² per head at very high design density.

Sprinkler Temperature Ratings — Colour Code

Temperature RatingTemperatureBulb ColourCommon Application
Ordinary57–77°CRed / OrangeOffices, hotels, hospitals
Intermediate79–107°CYellow / GreenGlass roofs, enclosed car parks
High121–149°CBlueSteam areas, dryers
Extra High163–191°CPurpleOvens, internal flues
Ultra High204–246°CBlackHighly specialised applications

Precise Spacing Requirements (NFPA 13)

  • Minimum distance between sprinklers: 1.8 m (to prevent cold-soldering between adjacent heads)
  • Maximum distance from wall: Half of maximum spacing (Light Hazard: 2.3 m; Ordinary: 2.3 m)
  • Clearance below deflector: No obstruction within 460 mm below deflector
  • Structural beams: Beams deeper than 250 mm are treated as walls and require an additional sprinkler
  • Sloped ceilings: Additional sprinkler required at the ridge
  • Concealed spaces: Electrical rooms and false ceilings exceeding 100 mm depth require sprinkler coverage

Portable Fire Extinguishers — Detailed Requirements

Per NFPA 10 and the UAE Civil Defence Code, portable extinguishers are mandatory in all facilities regardless of sprinkler installation:

Class A — Ordinary Combustibles

  • Light Hazard: 2-A rating per 278 m², max travel distance 23 m
  • Ordinary Hazard: 2-A rating per 139 m², max travel distance 23 m
  • Extra Hazard: 4-A rating per 93 m², max travel distance 15 m

Class B — Flammable Liquids & Gases

  • 5-B to 10-B rating: Max travel distance 15 m
  • 10-B and above: Max travel distance 9 m

Class K — Commercial Kitchens

  • Wet chemical extinguisher specifically rated for commercial cooking
  • One required per cooking appliance using oils or fats with capacity above 2 litres
  • Maximum travel distance: 9 m from the appliance

General Installation Requirements

  • Mounting height: Handle at 1.0–1.5 m from floor for extinguishers under 18 kg
  • Securing: Wall bracket or dedicated cabinet — never placed directly on floor
  • Monthly check: Visual inspection of seal and pressure gauge
  • Annual inspection: By a certified technician
  • Pressure test: Every 5 years for dry powder and CO₂; every 12 years for foam

Fire Pumps — NFPA 20 & UAE Code Requirements

The pump is the heart of the sprinkler system — among the most critical elements in the suppression network:

  • Main electric pump: Designed to deliver the required pressure and flow at all design points
  • Diesel backup pump: Mandatory where fire could interrupt the electricity supply. Must operate without mains power
  • Jockey pump: Small pressure-maintaining pump that detects minor leaks in the system
  • Water storage tank: Must provide 30–60 minutes of full-system operation (per design)
  • Testing: Weekly no-flow start test + full annual performance test

Practical Examples

General Storage Warehouse 2,000 m² (Ordinary Hazard Group 2): 2,000 ÷ 12.1 = 166 sprinkler heads minimum. Design density: 12.2 L/min/m². Design area: 139 m² → pump flow: 139 × 12.2 = 1,696 L/min minimum.
Commercial Office 500 m² (Light Hazard): 500 ÷ 18.6 = 27 sprinkler heads. Design density: 4.1 L/min/m². Required flow: 139 × 4.1 = 570 L/min.
Extinguishers for 1,000 m² Warehouse (OH1): 1,000 ÷ 139 = 7.2 → minimum 8 extinguishers rated 2-A, distributed so no point exceeds 23 m travel distance to the nearest unit.

System Integration in the UAE

  • Sprinklers + Alarm: Water flow from any head activates the flow switch, sending a signal to the alarm panel
  • Pumps + Alarm: Pumps start automatically on pressure drop in the system
  • Isolation valves: Must remain open at all times and be electronically monitored (tamper switch)
  • Tank + BMS: Tank level monitoring integrated into the building management system

Regulatory References