Estidama tool
Estidama Water Reduction (PW-R1 / PW-1)
Enter the quantity of each fixture and the flow rate of the model you actually specified. The tool compares the design daily volume against the baseline and returns the reduction achieved.
🧪 Example figures
Illustrative only — not typical values, not a recommendation. Replace with your own.
↳ Three rows sit AT the baseline and claim nothing — PBRS’s urinal and public-tap figures are aggressive and most catalogue models do not beat them.
📋 PW-R1 requires predicted consumption to be no greater than the baseline. It awards no points.
| Fixture | Baseline | Durationassumption | Uses/dayassumption | Qty | Your design |
|---|---|---|---|---|---|
| Water Closet (Dual Flush) | 6 L/flush6/4 liters/flushing cycle (full/low) | 1 | 3 | ||
| Urinal (Commercial) | 0.5 L/flush0.5 liters/flushing cycle | 1 | 2 | ||
| Lavatory Faucet (Private) | 6 L/min6 liters/min at 417.7 kPa | 0.25 | 3 | ||
| Lavatory Faucet (Public) | 1.9 L/min1.9 liters/min at 417.7 kPa | 0.25 | 3 | ||
| Kitchen Sink | 6 L/min6 liters/min at 417.7 kPa | 1 | 1 | ||
| Shower Head | 9.5 L/min9.5 liters/min at 551.6 kPa | 5 | 1 | ||
| Bidet | 6 L/min6 liters/min | 0.25 | 2 |
- Water Closet (Dual Flush): The standard publishes a pair (full/low). The blend ratio between them comes from the authority's own calculator, so this tool uses the full-flush figure, which is the more conservative of the two.
Design flow must come from the manufacturer datasheet for the specified model — not a typical value.